Sub-Array Record (subArray)
The normal use for the subArray record type is to obtain sub-arrays from waveform records. Setting either the number of elements (NELM) or index (INDX) fields causes the record to be processed anew so that applications in which the length and position of a sub-array in a waveform record vary dynamically can be implemented using standard EPICS operator interface tools.
The first element of the sub-array, that at location INDX in the referenced waveform record, can be displayed as a scalar, or the entire subarray (of length NELM) can be displayed in the same way as a waveform record. If there are fewer than NELM elements in the referenced waveform after the INDX, only the number of elements actually available are returned, and the number of elements read field (NORD) is set to reflect this. This record type does not support writing new values into waveform records.
Parameter Fields
The record-specific fields are described below, grouped by functionality.
Scan Parameters
The subArray record has the standard fields for specifying under what circumstances the record will be processed. These fields are listed in Scan Fields.
Read Parameters
The subArray’s input link (INP) should be configured to reference the Waveform record. It should specify the VAL field of a Waveform record. The INP field can be a channel access link, in addition to a database link.
In addition, the DTYP field must specify a device support module. Currently, the
only device support module is Soft Channel
.
Field |
Summary |
Type |
DCT |
Default |
Read |
Write |
CA PP |
---|---|---|---|---|---|---|---|
INP |
Input Specification |
INLINK |
Yes |
Yes |
Yes |
No |
|
DTYP |
Device Type |
DEVICE |
Yes |
Yes |
Yes |
No |
Array Parameters
These parameters determine the number of array elements (the array length) and the data type of those elements. The Field Type of Value (FTVL) field determines the data type of the array.
The user specifies the maximum number of elements that can be read into the subarray in the MALM field. This number should normally be equal to the number of elements of the Waveform array (found in the Waveform’s NELM field). The MALM field is used to allocate memory. The subArray’s Number of Elements (NELM) field is where the user specifies the actual number of elements that the subArray will extract. It should of course be no greater than MALM; if it is, the record processing routine sets it equal to MALM.
The INDX field determines the offset of the subArray record’s array in relation to the Waveform’s. For instance, if INDX is 2, then the subArray will read NELM elements starting with the third element of the Waveform’s array. Thus, it equals the index number of the Waveform’s array.
The actual sub-array is referenced by the VAL field.
Field |
Summary |
Type |
DCT |
Default |
Read |
Write |
CA PP |
---|---|---|---|---|---|---|---|
FTVL |
Field Type of Value |
MENU menuFtype |
Yes |
Yes |
No |
No |
|
VAL |
Value |
Set by FTVL |
No |
Yes |
Yes |
Yes |
|
MALM |
Maximum Elements |
ULONG |
Yes |
1 |
Yes |
No |
No |
NELM |
Number of Elements |
ULONG |
Yes |
1 |
Yes |
Yes |
Yes |
INDX |
Substring Index |
ULONG |
Yes |
Yes |
Yes |
Yes |
Operator Display Parameters
These parameters are used to present meaningful data to the operator. They display the value and other parameters of the subarray record either textually or graphically.
EGU is a string of up to 16 characters describing the engineering units (if any)
of the values which the subArray holds. It is retrieved by the get_units()
record support routine.
The HOPR and LOPR fields set the upper and lower display limits for the
sub-array elements. Both the get_graphic_double()
and get_control_double()
record support routines retrieve these fields.
The PREC field determines the floating point precision with which to display
VAL. It is used whenever the get_precision()
record support routine is
called.
See Fields Common to All Record Types for more on the record name (NAME) and description (DESC) fields.
Field |
Summary |
Type |
DCT |
Default |
Read |
Write |
CA PP |
---|---|---|---|---|---|---|---|
EGU |
Engineering Units |
STRING [16] |
Yes |
Yes |
Yes |
No |
|
HOPR |
High Operating Range |
DOUBLE |
Yes |
Yes |
Yes |
No |
|
LOPR |
Low Operating Range |
DOUBLE |
Yes |
Yes |
Yes |
No |
|
PREC |
Display Precision |
SHORT |
Yes |
Yes |
Yes |
No |
|
NAME |
Record Name |
STRING [61] |
No |
Yes |
No |
No |
|
DESC |
Descriptor |
STRING [41] |
Yes |
Yes |
Yes |
No |
Alarm Parameters
The subarray record has the alarm parameters common to all record types. Alarm Fields lists the fields related to alarms that are common to all record types.
Run-time Parameters
These fields are not configurable by the user. They are used for the record’s internal processing or to represent the current state of the record.
The NORD field holds the number of elements that were actually read into the array. It will be less than NELM whenever the sum of the NELM and INDX fields exceeds the number of existing elements found in the source array.
BPTR contains a pointer to the record’s array.
Field |
Summary |
Type |
DCT |
Default |
Read |
Write |
CA PP |
---|---|---|---|---|---|---|---|
NORD |
Number elements read |
LONG |
No |
Yes |
No |
No |
|
BPTR |
Buffer Pointer |
NOACCESS |
No |
No |
No |
No |
Record Support
Record Support Routines
init_record
long (*init_record)(struct dbCommon *precord, int pass)
Using MALM and FTVL, space for the array is allocated. The array address is
stored in BPTR. This routine checks to see that device support is available and
a device support read routine is defined. If either does not exist, an error
message is issued and processing is terminated. If device support includes
init_record()
, it is called.
process
long (*process)(struct dbCommon *precord)
See “Record Processing”.
cvt_dbaddr
long (*cvt_dbaddr)(struct dbAddr *paddr)
This is called by dbNameToAddr()
. It makes the dbAddr structure refer to the
actual buffer holding the result.
get_array_info
long (*get_array_info)(struct dbAddr *paddr, long *no_elements, long *offset)
Retrieves NORD.
put_array_info
long (*put_array_info)(struct dbAddr *paddr, long nNew)
Sets NORD.
get_graphic_double
long (*get_graphic_double)(struct dbAddr *paddr, struct dbr_grDouble *p)
For the elements in the array, this routine routines HOPR and LOPR. For the INDX
field, this routine returns MALM - 1 and 0. For NELM, it returns MALM and 1. For
other fields, it calls recGblGetGraphicDouble()
.
get_control_double
long (*get_control_double)(struct dbAddr *paddr, struct dbr_ctrlDouble *p)
For array elements, this routine retrieves HOPR and LOPR. Otherwise,
recGblGetControlDouble()
is called.
get_units
long (*get_units)(struct dbAddr *paddr, char *units)
Retrieves EGU.
get_precision
long (*get_precision)(const struct dbAddr *paddr, long *precision)
Retrieves PREC.
Record Processing
Routine process implements the following algorithm:
Check to see that the appropriate device support module exists. If it doesn’t, an error message is issued and processing is terminated with the PACT field still set to TRUE. This ensures that processes will no longer be called for this record. Thus error storms will not occur.
Sanity check NELM and INDX. If NELM is greater than MALM it is set to MALM. If INDX is greater than or equal to MALM it is set to MALM-1.
Call the device support’s
read_sa()
routine. This routine is expected to place the desired sub-array at the beginning of the buffer and set NORD to the number of elements of the sub-array that were read.If PACT has been changed to TRUE, the device support read operation has started but has not completed writing the new value. In this case, the processing routine merely returns, leaving PACT TRUE. Otherwise, process sets PACT TRUE at this time. This asynchronous processing logic is not currently used but has been left in place.
Check to see if monitors should be invoked.
Alarm monitors are invoked if the alarm status or severity has changed.
Archive and value change monitors are always invoked.
NSEV and NSTA are reset to 0.
Scan forward link if necessary, set PACT FALSE, and return.
Device Support
Fields Of Interest To Device Support
The device support routines are primarily interested in the following fields:
Field |
Summary |
Type |
DCT |
Default |
Read |
Write |
CA PP |
---|---|---|---|---|---|---|---|
PACT |
Record active |
UCHAR |
No |
Yes |
No |
No |
|
DPVT |
Device Private |
NOACCESS |
No |
No |
No |
No |
|
UDF |
Undefined |
UCHAR |
Yes |
1 |
Yes |
Yes |
Yes |
NSEV |
New Alarm Severity |
MENU menuAlarmSevr |
No |
Yes |
No |
No |
|
NSTA |
New Alarm Status |
MENU menuAlarmStat |
No |
Yes |
No |
No |
|
INP |
Input Specification |
INLINK |
Yes |
Yes |
Yes |
No |
|
FTVL |
Field Type of Value |
MENU menuFtype |
Yes |
Yes |
No |
No |
|
MALM |
Maximum Elements |
ULONG |
Yes |
1 |
Yes |
No |
No |
NELM |
Number of Elements |
ULONG |
Yes |
1 |
Yes |
Yes |
Yes |
INDX |
Substring Index |
ULONG |
Yes |
Yes |
Yes |
Yes |
|
BPTR |
Buffer Pointer |
NOACCESS |
No |
No |
No |
No |
|
NORD |
Number elements read |
LONG |
No |
Yes |
No |
No |
Device Support Routines (devSASoft.c)
Device support consists of the following routines:
long report(int level)
This optional routine is called by the IOC command dbior
and is passed the
report level that was requested by the user.
It should print a report on the state of the device support to stdout.
The level
parameter may be used to output increasingly more detailed
information at higher levels, or to select different types of information with
different levels.
Level zero should print no more than a small summary.
long init(int after)
This optional routine is called twice at IOC initialization time.
The first call happens before any of the init_record()
calls are made, with
the integer parameter after
set to 0.
The second call happens after all of the init_record()
calls have been made,
with after
set to 1.
init_record
long init_record(subArrayRecord *prec)
This routine is called by the record support init_record()
routine.
read_sa
long read_sa(subArrayRecord *prec)
Enough of the source waveform is read into BPTR, from the beginning of the source, to include the requested sub-array. The sub-array is then copied to the beginning of the buffer. NORD is set to indicate how many elements of the sub-array were acquired.
Device Support For Soft Records
Only the device support module Soft Channel
is currently provided.
Soft Channel
INP is expected to point to an array field of a waveform record or similar.