64bit Integer Output Record (int64out)
This record type is normally used to send an integer value of up to 64 bits to an output device. The record supports alarm, drive, graphics and control limits.
This record type was included in base.dbd beginning with epics-base 3.16.1 .
Parameter Fields
The record-specific fields are described below.
Output Value Determination
These fields control how the record determines the value to be output when it gets processed:
Field |
Summary |
Type |
DCT |
Default |
Read |
Write |
CA PP |
---|---|---|---|---|---|---|---|
OMSL |
Output Mode Select |
MENU menuOmsl |
Yes |
Yes |
Yes |
No |
|
DOL |
Desired Output Link |
INLINK |
Yes |
Yes |
Yes |
No |
|
DRVH |
Drive High Limit |
INT64 |
Yes |
Yes |
Yes |
Yes |
|
DRVL |
Drive Low Limit |
INT64 |
Yes |
Yes |
Yes |
Yes |
|
VAL |
Desired Output |
INT64 |
Yes |
Yes |
Yes |
Yes |
The following steps are performed in order during record processing.
Fetch Value
The OMSL menu field is used to determine whether the DOL link field should be used during processing or not:
If OMSL is
supervisory
the DOL link field is not used. The new output value is taken from the VAL field, which may have been set from elsewhere.If OMSL is
closed_loop
the DOL link field is used to obtain a value.
Drive Limits
The output value is clipped to the range DRVL to DRVH inclusive, provided that DRVH > DRVL. The result is copied into the VAL field.
Output Specification
These fields control where the record will read data from when it is processed:
Field |
Summary |
Type |
DCT |
Default |
Read |
Write |
CA PP |
---|---|---|---|---|---|---|---|
DTYP |
Device Type |
DEVICE |
Yes |
Yes |
Yes |
No |
|
OUT |
Output Specification |
OUTLINK |
Yes |
Yes |
Yes |
No |
The DTYP field selects which device support layer should be responsible for
writing output data.
The int64out device support layers provided by EPICS Base are documented in the
“Device Support” section.
External support modules may provide additional device support for this record
type.
If not set explicitly, the DTYP value defaults to the first device support that
is loaded for the record type, which will usually be the Soft Channel
support
that comes with Base.
The OUT link field contains a database or channel access link or provides hardware address information that the device support uses to determine where the output data should be sent to.
Operator Display Parameters
These parameters are used to present meaningful data to the operator. They do not affect the functioning of the record.
DESC is a string that is usually used to briefly describe the record.
EGU is a string of up to 16 characters naming the engineering units that the VAL field represents.
The HOPR and LOPR fields set the upper and lower display limits for the VAL, HIHI, HIGH, LOW, and LOLO fields.
Field |
Summary |
Type |
DCT |
Default |
Read |
Write |
CA PP |
---|---|---|---|---|---|---|---|
DESC |
Descriptor |
STRING [41] |
Yes |
Yes |
Yes |
No |
|
EGU |
Units name |
STRING [16] |
Yes |
Yes |
Yes |
No |
|
HOPR |
High Operating Range |
INT64 |
Yes |
Yes |
Yes |
No |
|
LOPR |
Low Operating Range |
INT64 |
Yes |
Yes |
Yes |
No |
Alarm Limits
The user configures limit alarms by putting numerical values into the HIHI, HIGH, LOW and LOLO fields, and by setting the associated alarm severities in the corresponding HHSV, HSV, LSV and LLSV menu fields.
The HYST field controls hysteresis to prevent alarm chattering from an input signal that is close to one of the limits and suffers from significant readout noise.
The LALM field is used by the record at run-time to implement the alarm limit hysteresis functionality.
Field |
Summary |
Type |
DCT |
Default |
Read |
Write |
CA PP |
---|---|---|---|---|---|---|---|
HIHI |
Hihi Alarm Limit |
INT64 |
Yes |
Yes |
Yes |
Yes |
|
HIGH |
High Alarm Limit |
INT64 |
Yes |
Yes |
Yes |
Yes |
|
LOW |
Low Alarm Limit |
INT64 |
Yes |
Yes |
Yes |
Yes |
|
LOLO |
Lolo Alarm Limit |
INT64 |
Yes |
Yes |
Yes |
Yes |
|
HHSV |
Hihi Severity |
MENU menuAlarmSevr |
Yes |
Yes |
Yes |
Yes |
|
HSV |
High Severity |
MENU menuAlarmSevr |
Yes |
Yes |
Yes |
Yes |
|
LSV |
Low Severity |
MENU menuAlarmSevr |
Yes |
Yes |
Yes |
Yes |
|
LLSV |
Lolo Severity |
MENU menuAlarmSevr |
Yes |
Yes |
Yes |
Yes |
|
HYST |
Alarm Deadband |
INT64 |
Yes |
Yes |
Yes |
No |
|
LALM |
Last Value Alarmed |
INT64 |
No |
Yes |
No |
No |
Monitor Parameters
These parameters are used to determine when to send monitors placed on the VAL field. The monitors are sent when the current value exceeds the last transmitted value by the appropriate deadband. If these fields are set to zero, a monitor will be triggered every time the value changes; if set to -1, a monitor will be sent every time the record is processed.
The ADEL field sets the deadband for archive monitors (DBE_LOG
events), while
the MDEL field controls value monitors (DBE_VALUE
events).
The remaining fields are used by the record at run-time to implement the record monitoring deadband functionality.
Field |
Summary |
Type |
DCT |
Default |
Read |
Write |
CA PP |
---|---|---|---|---|---|---|---|
ADEL |
Archive Deadband |
INT64 |
Yes |
Yes |
Yes |
No |
|
MDEL |
Monitor Deadband |
INT64 |
Yes |
Yes |
Yes |
No |
|
ALST |
Last Value Archived |
INT64 |
No |
Yes |
No |
No |
|
MLST |
Last Val Monitored |
INT64 |
No |
Yes |
No |
No |
Simulation Mode Parameters
The following fields are used to operate the record in simulation mode.
If SIMM (fetched through SIML) is YES, the record is put in SIMS severity and the value is written through SIOL. SSCN sets a different SCAN mechanism to use in simulation mode. SDLY sets a delay (in sec) that is used for asynchronous simulation processing.
See Output Simulation Fields for more information on simulation mode and its fields.
Field |
Summary |
Type |
DCT |
Default |
Read |
Write |
CA PP |
---|---|---|---|---|---|---|---|
SIML |
Simulation Mode Link |
INLINK |
Yes |
Yes |
Yes |
No |
|
SIMM |
Simulation Mode |
MENU menuYesNo |
No |
Yes |
Yes |
No |
|
SIOL |
Simulation Output Link |
OUTLINK |
Yes |
Yes |
Yes |
No |
|
SIMS |
Simulation Mode Severity |
MENU menuAlarmSevr |
Yes |
Yes |
Yes |
No |
|
SDLY |
Sim. Mode Async Delay |
DOUBLE |
Yes |
-1.0 |
Yes |
Yes |
No |
SSCN |
Sim. Mode Scan |
MENU menuScan |
Yes |
65535 |
Yes |
Yes |
No |
Invalid Alarm Output Action
Whenever an output record is put into INVALID alarm severity, IVOA specifies the action to take.
Continue normally
(default)Write the value. Same as if severity is lower than INVALID.
Don't drive outputs
Do not write value.
Set output to IVOV
Set VAL to IVOV, then write the value.
Field |
Summary |
Type |
DCT |
Default |
Read |
Write |
CA PP |
---|---|---|---|---|---|---|---|
IVOA |
INVALID output action |
MENU menuIvoa |
Yes |
Yes |
Yes |
No |
|
IVOV |
INVALID output value |
INT64 |
Yes |
Yes |
Yes |
No |
Record Support
Record Support Routines
The following are the record support routines that would be of interest
to an application developer.
Other routines are the get_units
, get_graphic_double
,
get_alarm_double
and get_control_double
routines, which are used to
collect properties from the record for the complex DBR data structures.
init_record
This routine first initializes the simulation mode mechanism by setting SIMM if SIML is a constant.
It then checks if the device support and the device support’s
write_int64out
routine are defined.
If either one does not exist, an error message is issued
and processing is terminated.
If DOL is a constant, then VAL is initialized with its value and UDF is set to FALSE.
If device support includes init_record
, it is called.
Finally, the deadband mechanisms for monitors and level alarms are initialized.
process
See next section.
Record Processing
Routine process
implements the following algorithm:
Check to see that the appropriate device support module and its
write_int64out
routine are defined. If either one does not exist, an error message is issued and processing is terminated with the PACT field set to TRUE, effectively blocking the record to avoid error storms.Check PACT. If PACT is FALSE, do the following:
Determine value, honoring closed loop mode: if DOL is not a CONSTANT and OMSL is CLOSED_LOOP then get value from DOL setting UDF to FALSE in case of success, else use the VAL field.
Call
convert
: if drive limits are defined then force value to be within those limits.
Check UDF and level alarms: This routine checks to see if the record is undefined (UDF is TRUE) or if the new VAL causes the alarm status and severity to change. In the latter case, NSEV, NSTA and LALM are set. It also honors the alarm hysteresis factor (HYST): the value must change by at least HYST between level alarm status and severity changes.
Check severity and write the new value. See Invalid Output Action Fields for details on how invalid alarms affect output records.
If PACT has been changed to TRUE, the device support signals asynchronous processing: its
write_int64out
output routine has started, but not completed writing the new value. In this case, the processing routine merely returns, leaving PACT TRUE.Check to see if monitors should be invoked:
Alarm monitors are posted if the alarm status or severity have changed.
Archive and value change monitors are posted if ADEL and MDEL conditions (see “Monitor Parameters”) are met.
NSEV and NSTA are reset to 0.
Scan (process) forward link if necessary, set PACT to FALSE, and return.
Device Support
Device Support Interface
The record requires device support to provide an entry table (dset) which defines the following members:
typedef struct {
long number;
long (*report)(int level);
long (*init)(int after);
long (*init_record)(int64outRecord *prec);
long (*get_ioint_info)(int cmd, int64outRecord *prec, IOSCANPVT *piosl);
long (*write_int64out)(int64outRecord *prec);
} int64outdset;
The module must set number
to at least 5, and provide a pointer to its
write_int64out()
routine; the other function pointers may be NULL
if their
associated functionality is not required for this support layer.
Most device supports also provide an init_record()
routine to configure the
record instance and connect it to the hardware or driver support layer.
The individual routines are described below.
Device Support Routines
long report(int level)
This optional routine is called by the IOC command dbior
and is passed the
report level that was requested by the user.
It should print a report on the state of the device support to stdout.
The level
parameter may be used to output increasingly more detailed
information at higher levels, or to select different types of information with
different levels.
Level zero should print no more than a small summary.
long init(int after)
This optional routine is called twice at IOC initialization time.
The first call happens before any of the init_record()
calls are made, with
the integer parameter after
set to 0.
The second call happens after all of the init_record()
calls have been made,
with after
set to 1.
long init_record(int64outRecord *prec)
This optional routine is called by the record initialization code for each
int64out record instance that has its DTYP field set to use this device support.
It is normally used to check that the OUT address is the expected type and that
it points to a valid device, to allocate any record-specific buffer space and
other memory, and to connect any communication channels needed for the
write_int64out()
routine to work properly.
long get_ioint_info(int cmd, int64outRecord *prec, IOSCANPVT *piosl)
This optional routine is called whenever the record’s SCAN field is being
changed to or from the value I/O Intr
to find out which I/O Interrupt Scan
list the record should be added to or deleted from.
If this routine is not provided, it will not be possible to set the SCAN field
to the value I/O Intr
at all.
The cmd
parameter is zero when the record is being added to the scan list,
and one when it is being removed from the list.
The routine must determine which interrupt source the record should be connected
to, which it indicates by the scan list that it points the location at *piosl
to before returning.
It can prevent the SCAN field from being changed at all by returning a non-zero
value to its caller.
In most cases the device support will create the I/O Interrupt Scan lists that
it returns for itself, by calling void scanIoInit(IOSCANPVT *piosl)
once for
each separate interrupt source.
That routine allocates memory and inializes the list, then passes back a pointer
to the new list in the location at *piosl
.
When the device support receives notification that the interrupt has occurred,
it announces that to the IOC by calling void scanIoRequest(IOSCANPVT iosl)
which will arrange for the appropriate records to be processed in a suitable
thread.
The scanIoRequest()
routine is safe to call from an interrupt service routine
on embedded architectures (vxWorks and RTEMS).
long write_int64out(int64outRecord *prec)
This essential routine is called when the record wants to write a new value to the addressed device. It is responsible for performing (or at least initiating) a write operation, using the value from the record’s VAL field.
If the device may take more than a few microseconds to accept the new value,
this routine must never block (busy-wait), but use the asynchronous
processing mechanism.
In that case it signals the asynchronous operation by setting the record’s
PACT field to TRUE before it returns, having arranged for the record’s
process()
routine to be called later once the write operation is over.
When that happens, the write_int64out()
routine will be called again with
PACT still set to TRUE; it should then set it to FALSE to indicate the write
has completed, and return.
A return value of zero indicates success, any other value indicates that an error occurred.
Extended Device Support
…
Device Support For Soft Records
Two soft device support modules, Soft Channel and Soft Callback Channel, are provided for output records not related to actual hardware devices. The OUT link type must be either a CONSTANT, DB_LINK, or CA_LINK.
Soft Channel
This module writes the current value using the record’s VAL field.
write_int64out
calls dbPutLink
to write the current value.
Soft Callback Channel
This module is like the previous except that it writes the current value using asynchronous processing that will not complete until an asynchronous processing of the target record has completed.